Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
153
Event
ID
Description Error
Meaning
65 KW
CASC
Configured,CASC AI
Configured
The Cascade control function was configured to use the kW
analog input but an Cascade analog input was configured also.
With this configuration, only the kW analog input is used for the
Cascade controller.
66 Remote
Casc
Configured, No AI
The Remote Cascade set point control function was configured
but no Remote Cascade set point analog input was configured.
67
Inlet Pres CASC Config,
CASC AI Config
The Cascade control function was configured to use the Inlet
Pressure analog input but an Cascade analog input was
configured also. With this configuration, only the Inlet Pressure
analog input is used for the Cascade controller.
68
Exhaust Press CASC
Config, CASC AI Config
The Cascade control function was configured to use the Exhaust
Pressure analog input but an Cascade analog input was
configured also. With this configuration, only the Exhaust Pressure
analog input is used for the Cascade controller.
69
Exhaust Press CASC
Config, No AI Config
The Cascade control function was configured to use the Exhaust
Pressure analog input but no AI is configured to be the Exhaust
Pressure input
70 Remote
Speed
Configured, No AI
The remote speed set point control function was configured but no
remote speed set point analog input was configured.
71 Feed
Forward
Programmed, No AI
The Feed Forward function was configured but no Feed Forward
analog input is configured.
72
Sync and Sync/Load
Share Configured
Both the synchronizing analog input and the sync/load share or
load share analog inputs are configured. If the application needs
to perform both synchronizing and load sharing with analog
signals, only the sync/load sharing analog input needs to be
configured.
73
Load Share and
Frequency Arm Cnfg
Both the frequency arm/disarm function and the load share control
functions are configured. Only one of these modes can be
programmed — either freq arm/disarm OR Load Sharing.
74 Generator
Application,
No Tie Breaker
The unit is configured for a generator application but no utility tie
breaker contact input is configured. This is a requirement.
75 Generator
Application,
No Gen Breaker
The unit is configured for a generator application but no generator
breaker contact input is configured. This is a requirement.
76
Idle 1 in Critical Band
Either the Idle speed set point (when using Idle/Rated) or the Idle
1 set point (when using the Automatic Start sequence) is
configured within a critical speed avoidance band.
77
Idle 2 in Critical Band
The Idle 2 speed set point (when using the Automatic Start
sequence) is configured within a critical speed avoidance band.
78
Idle 3 in Critical Band
The Idle 3 speed set point (when using the Automatic Start
sequence) is configured within a critical speed avoidance band.
79
Min Control Speed <
Failed Speed Level
Either the Idle speed set point (when using Idle/Rated) or the Idle
1 set point (when using the Automatic Start sequence) is
configured lower than the Failed Speed Level for speed input 1 or
2.
80
Idle 1 Setpoint >
Minimum Governor
The Idle Speed setpoint is configured at a higher speed than the
minimum governor speed setpoint.