Explosion Hazard
Substitution of components may impair suitability for Class I,
Division 2 or Zone 2.
Explosion Hazard
The external ground lugs shown on the installation drawing must be
properly connected to ensure equipotential bonding. This is will
reduce the risk of electrostatic discharge in an explosive
atmosphere. Cleaning by hand or water spray must be performed
while the area is known to be non-hazardous to prevent an
electrostatic discharge in an explosive atmosphere.
Explosion Hazard
MOUNTING
The control must be mounted in a vertical position. The installer shall
ensure the maximum surrounding air temperature of the control does
not exceed 70˚C at the final location.
Explosion Hazard
Class I, Div 2 Groups A, B, C, D and Zone 2, Group IIC applications
require the input voltage to the relay contacts not exceed 32Vac rms
or 32Vdc.
Risque d'explosion
Ne pas enlever les couvercles, ni raccorder / débrancher les
prises électriques, sans vous en assurez auparavant que le
système a bien été mis hors tension; ou que vous vous
situez bien dans une zone non explosive.
Risque d'explosion
La substitution de composants peut rendre ce matériel
inacceptable pour les emplacements de Classe I, Division 2
et/ou Zone 2.
Risque d'explosion
Ne pas utiliser les bornes d’essai du block d’alimentation
ou des cartes de commande à moins de se trouver dans un
emplacement non dangereux.