Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
178
Each individual alarm condition is available through the Modbus links to monitor the control status. A
common alarm indication is also provided.
Relay indications can be programmed to indicate a 505 Common Alarm, in addition to the dedicated
Alarm Relay output.
The table below lists all the potential alarm conditions and their Event ID.
Table 5-1. ALARM Messages
Event
ID DESCRIPTION
MEANING
1
Speed Probe #1 Failed
Speed probe #1 failure—(< Failed Speed Level or 1 Vrms)
2
Speed Probe #2 Failed
Speed probe #2 failure—(< Failed Speed Level or 1 Vrms)
3
Remote Spd Input Failed
Remote Speed Setpt analog input failure (> 22 mA or < 2 mA)
4
Sync Input Failed
Sync analog input failure detected (> 22 mA or < 2 mA)
5
Load Share Input Failed
Load Share analog input failure detected (> 22 mA or < 2 mA)
6
KW Load Input Failed
KW analog input failure detected (> 22 mA or < 2 mA)
7
Cascade Input Failed
Cascade analog input failure detected (> 22 mA or < 2 mA)
8
Remote Cascade Input Failed
Remote Cascade Setpt analog input failure (> 22 mA or < 2 mA)
9
AUX Input Failed
Auxiliary analog input failure detected (> 22 mA or < 2 mA)
10
Remote AUX Input Failed
Remote Aux Setpt analog input failure (> 22 mA or < 2 mA)
11 Spare_11
N/A
12 Spare_12
N/A
13
Inlet Press Input Failed
Inlet Header Pressure analog input failure detected (> 22 mA or < 2
mA)
14
IH-A Input press AI FLT
Fault indication from hydraulic pressure unit A
15
IH-B Input press AI FLT
Fault indication from hydraulic pressure unit B
16
Feed-forward input failed
Feed-Forward analog input failure detected (> 22 mA or < 2 mA)
17
Remote Droop Fault
Remote Droop Setting analog input failure detected (> 22 mA or < 2
mA)
18
Remote KW Setpoint Failed
Remote KW Setpt analog input failure (> 22 mA or < 2 mA)
19
Exhaust Press Input Failed
Exhaust Pressure analog input failure detected (> 22 mA or < 2 mA)
20
Temp for Hot/Cold Starts Failed Temp for Hot/Cold analog input failure detected (> 22 mA or < 2 mA)
21
HP Valve Feedback Failed
HP position FDBK analog input failure detected (> 22 mA or < 2 mA)
22
HP2 Valve Feedback Failed
HP2 position FDBK analog input failure detected (> 22 mA or < 2
mA)
23
Isolated PID PV Failed
Isolated PV analog input failure detected (> 22 mA or < 2 mA)
24
Rem SP Isolated PID Failed
Rem Setpoint for Iso analog input failure detected (> 22 mA or < 2
mA)
25
Customer Input #1 Failed
Customer analog input 1 failure detected (> 22 mA or < 2 mA)
26
Customer Input #2 Failed
Customer analog input 2 failure detected (> 22 mA or < 2 mA)
27
Customer Input #3 Failed
Customer analog input 3 failure detected (> 22 mA or < 2 mA)
28
Start Temperature 1 Failed
Start Temp 1 analog input failure detected (> 22 mA or < 2 mA)
29
Start Temperature 2 Failed
Start Temp 2 analog input failure detected (> 22 mA or < 2 mA)
30 Extraction/Admission
Input
Failed
Ext/Adm analog input failure detected (> 22 mA or < 2 mA)
31
Remote Extr/Adm SP Input
Failed
Remote Ext/Adm Setpoint analog input failure detected (> 22 mA or
< 2 mA)
32
External alarm # 1
External Alarm #1 from contact input
33
External alarm # 2
External Alarm #2 from contact input
34
External alarm # 3
External Alarm #3 from contact input
35
External alarm # 4
External Alarm #4 from contact input
36
External alarm # 5
External Alarm #5 from contact input
37
External alarm # 6
External Alarm #6 from contact input
38
External alarm # 7
External Alarm #7 from contact input
39
External alarm # 8
External Alarm #8 from contact input
40
External alarm # 9
External Alarm #9 from contact input