Manual 35018V1
505XT Digital Control System for Steam Turbines
Woodward
152
Event
ID
Description Error
Meaning
48
Actuator 01 Readout
Error
The Actuator/Driver channel readout was configured for a function
that is not configured as used. Either the readout was mis-
configured or the function required is mis-configured. For example,
readout is configured for Cascade Set Point but Cascade Control
was not configured under the Cascade Program Block.
49
Actuator 02 Readout
Error
See "Actuator 01 Readout Error".
50
Max KW Load > Max
KW AI Scale
The KW Max Load setting was programmed at a higher value than
the maximum KW input (KW input at 20 mA).
51
Selected KW Source Not
Configured
Occurs when a Primary or Secondary kW Signal source has been
selected under Operating Parameters but that source is not
configured. For example, Primary kW Source is set as 'Analog
Input' but no analog input is configured as a kW Input.
52
Turbine Type Requires
LP Valve
The unit is configured for Extraction/Admission and requires an LP
Valve Driver to be configured
53
No LP Valve on this
Turbine Type
The unit is configured for as a Single Valve unit, but an LP Valve
Driver has been configured
54
Auxiliary Configured, No
AI
The Auxiliary control function was configured but no Auxiliary
analog input was configured.
55
KW AUX Configured,
AUX AI Configured
The Auxiliary control function was configured to use the kW
analog input but an Auxiliary analog input was configured also.
With this configuration, only the kW analog input is used for the
Auxiliary controller.
56 Remote
AUX
Configured, No AI
The Remote Auxiliary set point control function was configured but
no Remote Auxiliary set point analog input was configured.
57
Duplicate LP Configured There is more than 1 selection for the LP valve demand output
58
Wrong Product Model
Detected
The Hardware model number does not match the Application.
59
Alternate Mode Map
Error
The D1-D6 values defining the Steam Map that will result from
entering an alternate mode are incorrect. Either the sign (+/-) or
the magnitude (less than 1e-6) is incorrect on one of these terms.
For Exhaust Control modes, this is generally caused by incorrect
settings of the Inlet, Extraction, or Exhaust Max Flow values.
60 Spare60
N/A
61 Spare61
N/A
62 Spare62
N/A
63 Spare63
N/A
64 Cascade
Configured,
No
AI
The Cascade control function was programmed but no Cascade
analog input was configured.