4-2 | MVW3000
4
Technical Data
Table 4.1:
Recommended fuses
Inverter Rated
Current (A)
Fuse
40
3R
50
3R
60
3R
70
5R
80
5R
90
5R
100
5R
110
12R
125
12R
140
12R
160
12R
180
18R
200
18R
The standard panels supplied for the MVW3000 are suitable for connection to medium voltage circuits capable
to supply a maximum symmetrical short circuit current of 40 kA.
The standard panels supplied for the MVW3000 are suitable for connection to medium voltage circuits capable
to supply a maximum symmetrical short circuit current of 40 kA.
4.1.1 Panel Constructive Aspects
The panel is made with steel sheets painted and processed (cutting, holes, folding, chemical treatment, painting
and finishing) by WEG, ensuring the quality in all the levels of the manufacture process. The inverter parts that
are not painted are zinc plated or have another suitable treatment in order to assure their resistance against
corrosion.
Transformer and Circuit
Inverter
Control
Figure 4.2:
Panel of the 18-cell MVW3000 (Frame B6)
The MVW3000 panel is supplied, in its standard structure, with degree of protection IP41 (openings smaller than
10 mm and protected against ingress of vertical drops). They can be supplied with distinct degrees of protection
according to the customer’s needs.
The panel cooling is done by means of forced convection. The air enters through the opening on the panel front
doors, goes through the transformer windings and also the power heatsinks located in each power cell. The
hot air leaves through the top do painel, of the panel, where the exhaust fans are located, allowing maintenance
without the need to open the inverter doors.
Summary of Contents for MVW3000 A0040 V023
Page 2: ......
Page 4: ......
Page 5: ...User s Manual Series MVW3000 Language English Document 10004823674 00 Publication Date 03 2017...
Page 6: ...Summary of Reviews Version Review Description R00 First edition...
Page 12: ...1 4 MVW3000 1 Safety Notices...
Page 58: ...6 18 MVW3000 6 Installation Connection and Energization...