6-14 | MVW3000
6
Installation, Connection and Energization
H19-H20-H21
H16-H17-H18
H10-H11-H12
H13-H14-H15
H7-H8-H9
H4-H5-H6
H1-H2-H3
220 V
380 V
400 V
415 V
440 V
460 V
480 V
Primary Taps
Voltage
3
1
5
2
4
6
Q1
1
3
2
4
1
3
5
2
4
6
Q2
3~380 V
3~220 V
S6
S5
S1
S2
S3
N
S4
T2
H1
H2
H3
480/460/440/415/400/380/220-220 V
3000 VA
22
0 t
o 4
80 V
ac 5
0/
60 H
z
Thr
ee
-p
ha
se
po
w
er
s
upp
ly
Ve
nt
ila
tion
a
nd
c
on
tr
ol
Pr
e-
ch
arg
e
Figure 6.11:
Auxiliary power supply
6.3 ENERGIZATION, START-UP AND SAFE DE-ENERGIZATION
This section provides the following information:
How to check and prepare the inverter before powering-up.
How to power-up and verify the energization success.
How to operate the inverter when installed according to the standard project (refer to the
Section 6.2 ELECTRICAL
INSTALLATION on page 6-10
and the attached electric project).
How to de-energize the inverter safely.
6.3.1 Pre-power Checks
The inverter must have already been installed according to the
Chapter 6 INSTALLATION, CONNECTION AND
ENERGIZATION on page 6-1
. Even when the inverter electric project is different from the suggested one in the
attachment, the following recommendations are applicable.
DANGER!
Always disconnect all the power supplies before making any connections.
Although the inverter commands the opening of the input cubicle, there is no guarantee of its
opening and neither that no voltages are present.
DANGER!
Débranchez toujours toutes les alimentations avant d’effectuer des branchements.
Bien que l'onduleur commande l'ouverture de l'armoire d'entrée, il n'y a aucune garantie de son
ouverture et ni qu'aucune tensions sont présentes.
In order to open the medium voltage cabinets, follow all the safe de-energization procedures.
Summary of Contents for MVW3000 A0040 V023