9-16 | MVW3000
9
Communication Networks
9-16 | MVW3000
Diagram:
Inverter
Basic variables
Parameters
Master
Serial connection
Variables
Figure 9.11:
Scheme of basic variables
Parameter/Variable Resolutions
During parameter reading/writing their decimal points are disregarded in the values received/sent via telegrams,
whereas the basic variables V04 (Serial Reference) and V08 (Motor Speed) that are standardized as 13 bit (0 to
8191).
Examples:
Writing: If the purpose is to change the P0100 content to 10.0 s, 100 must be sent (disregarding the decimal
point).
Reading: If 1387 (disregarding the decimal point) is read from P0409, them its value is 1.387.
Writing: in order to change V04 content to 900 rpm one must send:
V04 = 900 x 8191 = 4096
P0208
Assuming that P0208 = 1800 rpm
Reading: If 1242 is read from V08 the corresponding value is given by:
V08 = 1242 x P0208 = 273 rpm
8191
Assuming that P0208 = 1800 rpm
Character Format
1 start bit.
8 data bits (they codify text and transmission characters, taken from the 7-bit code, according to ISO 646 and
complemented for even parity [eighth bit]).
1 stop bit.
After the start bit goes the least significant bit:
START
B1
B2
B3
B4
B5
B6
B7
B8
STOP
Start
bit
Stop
bit
8 data bits
Summary of Contents for MVW3000 A0040 V023
Page 2: ......
Page 4: ......
Page 5: ...User s Manual Series MVW3000 Language English Document 10004823674 00 Publication Date 03 2017...
Page 6: ...Summary of Reviews Version Review Description R00 First edition...
Page 12: ...1 4 MVW3000 1 Safety Notices...
Page 58: ...6 18 MVW3000 6 Installation Connection and Energization...