TITANUS
RACK·SENS
®
1U
Installation Pipe System
TRS_A_06-en-e
Data: 03/09
6
– 3
Do not use pipe clips with rubber cores as these do not expand length-
wise and the pipes would sag or crack.
5. Close open pipe ends with an end cap.
After pipe installation is complete, check for the following:
-
air tightness (eg due to damage)
-
any faulty connections
-
correct design of the air sampling holes
Pipe
Clips
As a rule, plastic pipe clips, type 23, are used for the installation of pipe
systems (
∅
25mm). They do not allow for linear expansion and in areas
with high temperature variations the plastic pipe shells, type CLIC-PA
must be used. (see fig. 6.1).
plastic pipe clip
for air sam pling pipe
Typ CLIC-PA
for linear expansions
plastic pipe clip
for 25 m m air
sam pling pipe
type NG 23
standard
Fig. 6.1: Pipe clips
INSTRUCTION
INSTRUCTION