TITANUS
RACK·SENS
®
1U
Installation
TRS_A_05-en-e
Data: 03/09
5
– 15
5.2.11 Installation and connection of temperature sensors
Up to 5 type TS-1 temperature sensors can be connected to a TITANUS
RACK·SENS
®
1U device with an optional temperature module.
1
4
Fig. 5.15: Connection for temperature sensors
The temperature sensors should be connected as follows:
1. Attach the temperature sensors to the positions provided in cabinets
or on designated components with a cable strap or similar and feed
the cable through to the temperature sensor connection on the
TITANUS
RACK·SENS
®
1U
device.
2. Open the upper caged spring terminal at connection 1 for the tem-
perature sensors with a slotted screw driver max. 2.5 mm wide.
3. Feed a cable end sleeve belonging to the first temperature sensor
into the open connection terminal. When you pull out the screwdriver
again, the terminal will close.
4. Now open the lower caged spring terminal at connection 1 for the
temperature sensors on the TITANUS
RACK·SENS
®
1U
device and
feed the second cable end sleeve belonging to the first temperature
sensor into the open connection terminal.
5. Carry out the same process with the other temperature sensors.
6. The temperature sensor is wired according to the following circuit
connection.