TITANUS
RACK·SENS
®
1U
Product Description
TRS_A_01-en-e
Data: 03/09
1
– 1
1
Product
Description
1.1 Features of the TITANUS RACK·SENS
®
1U air sampling smoke detection
system
TITANUS
RACK·SENS
®
1U is the latest generation of the renowned
WAGNER air sampling smoke detection systems. TITANUS
RACK·SENS
®
1U
was specially developed for use in 19” server racks and
control cabinets.
Sensitivity
TITANUS
RACK·SENS
®
response threshold can be set between 0.1 or
0.5 % and 2 %/ obs./m, depending on the design. The setting is adjusted
at intervals of 0.1 % obs./m. Alarm forwarding is possible starting from
0.01% obs./m via an adjustable pre-warning threshold (10 – 80% of the
main alarm threshold). An optional bar graph provides a display sensitiv-
ity from 0.01% or 0.05% obs./m. The reliable
High-Power-Light- Source
in
TITANUS systems ensures uniform response behaviour for different
types of fires in accordance with EN54-7 and EN54-20.
Intelligent
signal
processing
The
TITANUS
RACK·SENS
®
1U features
LOGIC·SENS,
an
intelligent
signal processing for avoiding false alarms
.
Complex algorithms based
on numerous fire trials and decades of experience ensure a high level of
safety in differentiating between a false alarm and a fire event.
Safe
airflow
monitoring
PIPE·GUARD
, the comprehensive package for airflow monitoring, de-
tects safely malfunctions breakdowns such as pipe breakages or blocked
sampling holes.
Airflow monitoring is temperature-compensated and can be set to be air
pressure-dependent.
Plug and Play
Installation and commissioning of the TITANUS
RACK·SENS
®
1U are
simple with the Plug & Play function.
The TITANUS
RACK·SENS
®
1U detection unit is pre-set for standard ap-
plication usage. TITANUS
RACK·SENS
®
1U
is immediately ready for op-
eration once it has been connected to the mains or 24 V supply and is
properly commissioned.