TITANUS
RACK·SENS
®
1U
Product Description
1
– 2
Data: 03/09
TRS_A_01-en-e
Networking
If fitted with on optional network card, TITANUS
RACK·SENS
®
1U
de-
vices can be linked together in an Ethernet network. From a central point
the user can, for example, via VisuLAN T
®
monitor all connected units for
smoke levels, airflow values etc. In addition, the TITANUS
RACK·SENS
®
1U
can be integrated via the so-called OPC server into existing hazard
and alert building management systems.
Potential
free
contacts
TITANUS
RACK·SENS
®
1U
provides potential-free contacts for “main
alarm” and “pre alarm”, “fault”, “service blocked” and “released” as well
as for 5 programmable relays. The air sampling smoke detection system
interfaces there for collective and addressable
0F
1
status signal easily with
any type of central fire alarm system.
2.
Detection-
unit
TITANUS
RACK·SENS
®
1U can be fitted with an optional second detec-
tor to perform as a double knock system. Each detection unit includes 2
alarm thresholds (pre-alarm and main alarm) and is provided with a sen-
sibility of 0.1 or 0.5 % obs./m.
Shutdown
In order to carry out an object shutdown (electrical disconnection) a po-
tential-free relay contact is provided which can be cascaded with a high
power relay for shut down of high power server racks. Object shutdown is
essential to prevent potential re-ignition when a fire is being extinguished
after extinguishing gas concentration has depleted below effective levels.
Diagnostics
The optional DIAG 3 diagnostics device, provides quick and easy device
configuration and visualisation during commissioning, inspection and ser-
vicing. For diagnostics purposes events are stored in the TITANUS
RACK·SENS
®
1U.
Designing
detection
points
The respective project planning instructions for object protection in this
manual must be complied with when planning the TITANUS
RACK·SENS
®
1U
®
sampling points.
Patented
detection
points
WAGNER’s
patented aspiration reduction film sheets, clips and bande-
rols make assembly simple and comfortable and avoid whistling noises
during operation. Another advantage is the quick and easy identification
and monitoring of the aspiration sampling point diameters.
1
Via the address module of the particular CFAS