Commissioning
TRS_A_07-en-e
Data: 03/09
7
– 15
7.2.6
Setting the programmable relays and the temperature alarm
Settings
for
programmable relays
These settings enable the relays to become logically linked to the alarms
(“AND” or “OR”).
Settings
for
temperature alarms
The temperature alarms 1 -5 are continuously adjustable between 0 °C
and 100 °C.
In the example below relay 1will be activated on main alarm by detector
unit 1 (main alarm detector module 1) or temperature alarm 1.
TITANUS RACK·SENS
® -
°C
65,0
5
°C
64,0
4
°C
63,0
3
°C
62,0
2
°C
61,0
1
Temperature alarm
Temperature alarm 1
Temperature alarm 2
Temperature alarm 3
Temperature alarm 4
Temperature alarm 5
Logical OR
Logical AND
Fire alarm detector module 1
Relay 1
Action alarm detector module 1
Programmable relay
00000
Cancel
Accept
File
Record
Settings
Device-Selection
More
?
Bus elements B
Smoke level
Events
Settings A
Settings B
Status
Bus elements A
(Date , Time)
Fire alarm detector module 2
Action alarm detector module 2
Relay 2
Relay 3
Relay 4
Relay 5
Cancel
Reception
Serial No.
Accept
Fig. 7.7: Settings for programmable relays and temperature alarm