Commissioning
TITANUS
RACK·SENS
®
1U
7
– 10
Data: 03/09
TRS_A_07-en-e
7.2.4.3
Fault delay setting
You can set the delay period for air flow faults here.
Fault delay
Default fault delay
Setting intervals
1 s – 60 min
100 s
1 s
The default setting for the delay period is 100 seconds. Other delay peri-
ods should be set for areas with temporary fault levels (such as changes
in air pressure) in accordance with the duration of the fault level.
1 s - 60 min
fault
triggering
fault relay
7.2.4.4
Pre-warning period setting
You can set the pre-warning period for extinguisher activation here. The
pre-warning period delays extinguisher activation.
Pre-warning period
Default pre-warning
period
Setting intervals
0 s – 60 s
10 s
1 s
0 - 60 s
0 - 60 s
alarm delay
pre-warning period
alarm
triggering
the relays
triggering
for
extinguisher activation