Installation
TITANUS
RACK·SENS
®
1U
5
– 4
Data: 03/09
TRS_A_05-en-e
5.2.3 Connection for sampling pipe
sam pling pipe
1
Fig. 5.4:
TITANUS
RACK·SENS
®
1U
sampling pipe connection
Connection
for
sampling pipe
n
Insert the sampling pipe into the pipe connection provided in order to
connect the sampling pipe to the TITANUS
RACK·SENS
®
1U device.
The standard aspiration pipe AP-1 is only to be used in cabinets cooled
by re circulated air.
Under no circumstances use adhesive to connect the sampling pipe to
the pipe connection.
If wide variations in temperature are expected, the pipe must be fixed
additionally close to the device, so that the pipe does not come loose
due to fluctuations in length (see section 6.1).
Ensure that the sampling pipe (if longer than 15 cm) is securely fastened
to the cabinet with a pipe clip. If not, the pipe may detach itself from the
pipe connection due to mechanical stress.
INSTRUCTION
INSTRUCTION
INSTRUCTION