Technical Description
TITANUS
RACK·SENS
®
1U
2
– 16
Data: 03/09
TRS_A_02-en-e
2.3.1.1
Standard sampling pipe
50
m
m
7 mm
Fig. 2.11: Standard sampling pipe Type AP-1
The standard sampling pipe type AP-1 is especially designed for cabinets
cooled by re-circulated air. As any possible smoke fumes are evenly dis-
tributed in such cabinets, this standard sampling pipe can be used here
in order to save on installation expenses for a conventional pipe system.
By installing in the TITANUS
RACK·SENS
®
1U uppermost rack, the unit
should be cable to detect smoke, even in a case when ventilation fails as
smoke will typically climb upwards in the event of fire.
Only to be used for cabinets cooled by re-circulated air.
ATTENTION