TITANUS
RACK·SENS
®
1U
Installation
TRS_A_05-en-e
Data: 03/09
5
– 13
5. Now screw in the provided cable gland into the designated opening
in the door contact switch.
6. The door contact switch is wired according to the following circuit
connection.
Service / blk.
Alarm 2
Alarm 1
Pre Alarm 1
Pre Alarm 2
Fault
0V / 24V
-
Door Switch
Reset
Data B / A
-
Man.Release
-
Released
Temp. 1
Temp. 3
Temp. 2
Temp. 4
Temp. 5
Fi
re
P
a
n
e
l
F
ir
e
P
a
ne
l
E
x
ti
n
g.
M
o
du
le
T
e
m
p
.
S
e
ns
or
s
X1
X2
X3
X4
Relay 1
Relay 3
Relay 2
Relay 4
Relay 5
Re
la
y
s
X5
TITANUS
RAC K·SENS
®
Fig. 5.13: Wiring for door contact switch
7. When wiring the door contact switch, the contact in the switch should
be selected in such a way that it is closed when in an activated state.
These are terminals 13 and 14 in the type DS-1 door contact switch.
8. After connecting the circuit, the door contact switch cable connection
should be tightened in such way that the connection cable sits firmly
in the connection and cannot slip out.