Installation Pipe System
TITANUS
RACK·SENS
®
1HE
6
– 2
Data: 03/09
TRS_A_06-en-e
When installing TITANUS
RACK·SENS
®
1U and its components, special
attention must be paid to avoid damaging them through dropping tools or
installation material!
Cooling of the rack and its components must not be impaired due to in-
stallation of the TITANUS
RACK·SENS
®
1U unit and its components.
Installation Instructions
The pipe system must be designed according to the requirements of the
project and the pipe design guidelines (see chapter 4 "Pipe Design").
1. Cut the pipes with a pipe cutter or a metal saw. Chips must be re-
moved and rough edges trimmed.
2.
Before
gluing, remove any dirt and grease from the joints with the rec-
ommended cleaning agent. Glue the pipe ends to the corresponding
fittings so that they are airtight.
Air Sam-
pling Pipe,
halogen-
free
Air Sam-
pling Pipe
(PVC)
Cleaning
Agent
Adhesive Pipe
Cutter
ABSR-2518,
R-2519,
Tangit cleaner
Tangit adhe-
sive
pipe cutter or
38mm saw
3. Keep the pipe lengths and direction changes to a minimum. Elbows
and bends have an extremely high flow resistance. Use them only
where this is unavoidable. Should this be necessary, the pipe length
must then be reduced in relation to the fitted bends
0F
1
.
Sweep elbows should be used instead of elbows. If there are too many
direction changes, an air flow fault can occur in TITANUS
RACK·SENS
®
1U
and detection time can be affected.
4. The pipes must be installed in such a way that they do not sag or
move. They should be fixed with pipe clips
without
rubber core. The
space between the pipe clips should be no more than 80cm. Reduce
the space between clips to no more than 30cm if there are high tem-
perature variations.
1 An arc equals a straight piece of pipe of 0.3m
an elbow equals a straight piece of pipe of 1.5m
ATTENTION
INSTRUCTION