Design
TITANUS
RACK·SENS
®
1U
4 –
20
Data: 03/09
TRS_A_04-en-e
4.4.3.3 U-Pipe
system
1 Pipe system
TITANUS
RACK·SENS
®
1U
d
Fig. 4.14: U-pipe system, e.g. for equipment protection
Limit values
min. distance TITANUS
P
®
P
– T piece
0,2 m
max. distance TITANUS
P
®
P
– T piece
10 m
max. branch length
7,5 m
max. pipe length per pipe system
pipe
∅
25 mm
in addition to the pipe
∅
12 mm
15 m
8 x 3 m
max. number aspiration holes (n) per pipe system
10
maximum distance between the aspiration holes (d)
0,1 m
minimum distance between the aspiration holes (d)
4 m
Aspiration holes
Number of holes
2
4
6
8
10
∅
of all aspiration
holes
in mm
TP1F
2
PT
)
6,0 4,2 3,4 3,0 2,5
TP
2
PT
Opening diameter of the aspiration reduction film