TITANUS
RACK·SENS
®
1U
Installation
TRS_A_05-en-e
Data: 03/09
5
– 5
5.2.4 TITANUS
RACK·SENS
®
1U electrical connection
The TITANUS
RACK·SENS
®
1U device is connected to the mains supply
via a terminal strip at the rear of the device.
Field wiring is to be connected to the removable terminal blocks, which
are capable of handling wire sizes from a minimum of 0.5 mm
2
up to 1.0
mm
2
. The use of fire protection cable in a twisted pair configuration is ad-
vised.
DC
24
V
+
-
Version
24 V DC
Version
110-230 V AC
F2
,5
A
/ 25
0 V
11
0-23
0 V
A
C
Relays
Temp.
Sensors
Exting.
Module
Fire Panal
Fire Panal
X1
X2
X3
X4
X5
5
4
3
2
1
5
4
3
2
1
Released
0
Man.Release
Door Switch
Data B / A
V/ 24V
-
-
-
Reset
Fault
Pre Alarm 2
Pre Alarm 1
Alarm 2
Alarm 1
Service/blk.
Fig. 5.5: Terminal connection assignment on the TITANUS RACK·SENS
®
1U
device for mains or 24V supply