Technical Description
TITANUS
RACK·SENS
®
1U
2
– 2
Data: 03/09
TRS_A_02-en-e
2.1.1
Functional
description
1 U basic device
Fire detection
Fig. 2.2:
TITANUS
RACK·SENS
®
1 U base device for fire detection
The 1U basic device is a self-contained unit which can be used simply as
a detection unit, or can be extended through an external extin-
guisher/shutdown module which activates external extinguishing cylin-
ders.
Detection
options
z
2nd detection unit
z
Bargraph display (smoke)
z
Temperature display
z
Network capability
z
Mains supply/emergency power
Detection
and
alarm
The air sampling smoke detector (optional second detector with the same
or higher sensitivity) takes in air samples from the cabinet being moni-
tored via the pre-defined aspiration sampling points in a pipe or hose sys-
tem.
Once the pre- defined alarm thresholds are exceeded, a pre- or main
alarm will be indicated.