Maintenance
TITANUS
RACK·SENS
®
1U
8
– 8
Data: 03/09
TRS_A_08-en-e
If the airflow monitoring unit is suspected to be faulty, the TITANUS
RACK·SENS
®
1U unit needs to be returned to WAGNER Group GmbH
for repair.
If no deviations are detected in the process described during the
functional test, this confirms there is no defect in the air flow monitor-
ing system.
3. Carry out the adjustment process again with the connected pipe sys-
tem.
It is essential to record the adjustment type (air-pressure-dependent or
non-dependent) in the test log along with the air pressure and height
above sea level if required.
4. Monitor the actual air flow value during routine servicing or check it
during the next inspection at the latest.
All stored and actual device data as well as settings made using the di-
agnostics tool can be saved by the diagnostics software, or printed out
or saved as a log.
5. If there is a similar set point deviation as before, unfavourable envi-
ronmental factors are the cause for this deviation. If such negative
influences to the air flow monitoring system cannot be eliminated,
the air flow range should be enlarged.