Commissioning
TITANUS
RACK·SENS
®
1U
7
– 18
Data: 03/09
TRS_A_07-en-e
7.3
Data
logging
A basic device test is possible using the diagnostics tool. With its mes-
sage and status readouts, the diagnosis programme facilitates consid-
erably simplified servicing. The DIAG 3 can be attached to the TITANUS
RACK·SENS
®
1U using a device mount or be kept up to 3 m away along
a straight line (
±
10°) from the infrared interface.
Data is read via an infrared interface on the TITANUS
RACK·SENS
®
1U
using the DIAG 3, which is linked to the PC with a USB cable.
Since the infrared interface provides reception and transmission within a
range of 3 meters, several adjacent installed TITANUS
RACK·SENS
®
1U
units may appear in the device selection window (DIAG 3). Each one can
be addressed separately.
Diagnostics tool commissioning is described in the section 7 “Commis-
sioning”.
PC
DIAG 3
TITANUS
RACK·SENS
®
Connecting cable
USB cable
USB Port
Infrared interface for
DIAG 3 connection
“
”
Fig. 7.10: PC connection to
TITANUS
RACK·SENS
®
1U
It is recommended to print out the device log after completing the set-up
operation and keep it with the system documentation so that device set-
tings can be checked at a later date. Alternatively, the diagnostics file can
be saved.
Diagnostics file save:
Menu File, Save data
File type .di3
Service calls to:
WAGNER Group GmbH or our local representative
TIP