Technical Description
TITANUS
RACK·SENS
®
1U
2
– 12
Data: 03/09
TRS_A_02-en-e
2.2.4
Diagnostics
tool
Diagnostics tool
Infrared interface for
DIAG 3 connection
”
“
Connection for PC
Connection for
device
diagnostics
TITANUS
RACK·SENS
®
Fig. 2.8: Diagnostics tool to retrieve and store device data
The DIAG 3 diagnostics tool allows for configuration changes for the
TITANUS
RACK·SENS
®
1U
during commissioning. For maintenance and
servicing, the diagnostics software offers the option of displaying the
stored and current device status as well as fault messages from the
TITANUS
RACK·SENS
®
on a PC or laptop. Data is transmitted to the di-
agnostics device via the TITANUS
RACK·SENS
®
1U
infrared interface. A
USB cable is provided to transmit data from the diagnostics to the PC or
laptop.
It is recommended to copy all relevant set-up data during commissioning
and store this data together with the commissioning report.
The DIAG 3 diagnostics tool allows to delete stored fault signals at any
time. The signals remain stored in the TITANUS
RACK·SENS
®
1U until
they are reset. This enables short, sporadic faults to be evaluated (e.g.
after changing operating conditions).
TIP