Commissioning
TITANUS
RACK·SENS
®
1U
7
– 14
Data: 03/09
TRS_A_07-en-e
The settings in sections 7.2.5.1 and 7.2.5.2 do not apply in the case of
monitoring forced-air cooled cabinets and equipment.
7.2.5.1
Setting height above Normal Sea Level (NN)
The figure for the height above normal sea level is the value for the ac-
tual installation site of the TITANUS
RACK·SENS
®
1U above sea level.
The figure is input by using the diagnostics tool. The standard setting is 0
m. The figure has to be changed if an air pressure dependent adjustment
is desired (see Chap.7).
If the default setting for air pressure or the height above sea level is
changed, the air flow in the TITANUS
RACK·SENS
®
1U system must be
re-initiated by activating the Init button in the DIAG software.
7.2.5.2
Setting the current air pressure
The current air pressure for the monitoring area must be input by using
the TITANUS
RACK·SENS
®
1U
diagnostics tool if air pressure-dependent
adjustment is required.
The standard setting is 1013 hPa, corresponding to the average air
pressure at sea level.
7.2.5.3
Fan voltage setting
The default setting for the fan voltage is 9 V. When applications are criti-
cal, the fan voltage can be set higher in order to shorten the transport
time in the pipe system and to work against any air flow anomalies
caused by ventilation. Please contact
WAGNER
regarding any queries in
this respect.
Fan voltage
Default fan voltage
Setting intervals
9 V – 13,5 V
9 V
0,1 V
The settings can only be saved in the system configuration by pressing
the Init button in the DIAG software.
INSTRUCTION
ATTENTION
ATTENTION