Installation
TITANUS
RACK·SENS
®
1U
5
– 2
Data: 03/09
TRS_A_05-en-e
5.2
Installation
site
5.2.1 Mounting the TITANUS RACK·SENS
®
1U air flow
smoke sampling system
When deciding on the installation position, ensure the device is installed in
the highest rack position possible in the cabinet and that the indicators are
clearly visible.
When installing the TITANUS
RACK·SENS
®
1U, ensure that the device
is completely supported by rack rails. This may otherwise result in dam-
age to the device. Contact cabinet/rack manufacturer for suitable rack
rails.
TITANUS
RACK·SENS
®
cabinet rail
Fig. 5.1:
TITANUS
RACK·SENS
®
1U
installation
Aspiration
When installing
TITANUS
RACK·SENS
®
1U
ensure that the air outlet on the
top left-hand side of the device is not blocked.
A minimum gap of 1 cm must be kept from the surrounding components
when installing the device.
INSTRUCTION