wc_tx001903gb.fm
63
E 1100
Operation
4.25
Operating States of the Beckett Burner Controller
Burner states
The burner control has several states that it sequences through during normal
operation. These operating states are described below.
.
Standby
Run
Ignition
carryover
State
10
30
Operating
wc_gr007662
State
Action or Function
Standby
As soon as power is supplied to the burner control, the burner control
enters the standby state in which it will remain until there is a call for
heat or power is disconnected.
Valve-on
delay
(pre-time)
When the setpoint of the temperature controller is set to a temperature
higher than that of the heat transfer fluid, the output contacts of the tem-
perature controller close, completing a circuit between the two terminals
labeled “T” of the burner control. This is the call for heat. The burner
control enters the valve-on-delay state.
The valve-on-delay state lasts 15 seconds. During this state:
Power is sent to the burner motor.
Power is sent to the electrodes.
If the cad cell detects flame anytime during the valve-on-delay state,
the burner control goes into the lockout state.
Trial-for-
ignition
The trial-for-ignition state immediately follows the valve-on-delay state.
During this state:
The fuel shut-off valve is opened (energized).
Pressurized fuel atomizes at the burner nozzle.
The atomized fuel is ignited by the electrodes.
The burner fires and the flame is monitored by the cad cell.
If flame is detected, the burner control moves to the ignition carryover
state.
If flame is not detected within 15 seconds:
The burner control enters the lockout state.
Power is disconnected from the fuel shut-off valve, electrodes, and
the burner motor.
Summary of Contents for 5000620172
Page 19: ...E 1100 Safety Information wc_si000628gb fm 19 Notes ...
Page 20: ...Labels E 1100 20 wc_si000629gb fm 2 Labels 2 1 Label Locations wc_gr009588 ...
Page 105: ...ghi_tx001153gb fm 105 E 1100 Maintenance ...
Page 122: ...Technical Data E 1100 122 wc_td000476gb fm 10 5 Dimensions cm in wc_gr008706 ...
Page 133: ...wc_tx001673gb fm 133 Fuji Temperature Controller ...
Page 134: ...wc_tx001673gb fm 134 Fuji Temperature Controller ...
Page 151: ...E 1100 Schematics wc_tx001908gb fm 151 11 3 Burner System Circuit ...
Page 152: ...Schematics E 1100 152 wc_tx001908gb fm 11 4 Circulation System Circuit ghi_gr005662 ...
Page 153: ...E 1100 Schematics wc_tx001908gb fm 153 11 5 Rewind System Circuit ...
Page 158: ...Schematics E 1100 158 wc_tx001908gb fm 11 10 Genset DC Wiring Diagram ...
Page 160: ......
Page 161: ......