Accessories
E 1100
74
wc_tx001844gb.fm
5.6
Connecting a HX 100 Heat Exchanger
Requirements
Machine stopped
One HX 100 Heat Exchanger
Limitations
Maximum run (horizontal distance from HX to machine): 228 m (750 ft)
Maximum rise (vertical distance of HX above machine): 76 m (250 ft)
Maximum run at maximum rise: 215 m (707 ft)
Note:
The farther the HX is positioned from the parent machine, the more heat will
be lost through the hose. This may affect HX performance.
Procedure
Perform the procedure below to connect the Heat Exchanger to the machine.
1. Stop the parent machine temporarily.
2. Position the Heat Exchanger within the space to be heated.
This procedure continues on the next page.
0 – 76 m (250 ft)
0 – 228 m (750 ft)
0 – 215 m (707 ft)
wc_gr008096