4.3.2.6. Under Temperature Alarm
This is found under the settings / system / low temperature menu.
The Under Temperature Alarm refers to the temperatures set for each machine
zone.
The tolerance for the under temperature alarm is the number of degrees that each
zone has cooled below the set temperature before the alarm goes off.
The alarm tolerance range is 9ºF to 108ºF (5ºC to 60ºC). It is factory set at 27º F
(15º C).
If any zone enters the under temperature alarm zone, that zone will heat until the
set temperature is reached.
You can access this parameter with a password level of 2 or higher.
4.3.2.7. Maximum Temperature
This is found under the settings / system / maximum temperature menu.
The maximum temperature is the maximum programmed temperature value for
each zone. The maximum temperature range is 32º F to 446º F (0º C to 230º C). It is
factory set at 446º F (230º C).
You can access this parameter with a password level of 3 or higher.