77
Motor rotation direction changeover setting
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-03
Forward direction change
oFF (Forward rotation)
on (Reverse rotation)
- oFF
-
Forward direction change (E-03):
By setting the forward direction change to reverse rotation (E-03 = on), you can reverse the direction of the
rotation of the motor without changing the input wiring. When the reverse rotation prohibition mode setting is
set to prohibit opposite direction (b-08 = 2) while the forward direction change is reverse rotation (E-03 = on),
the forward rotation is prohibited.
Simulation mode setting
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-04 Simulation
mode
oFF (Without simulation operation)
on (With simulation operation)
- oFF
-
Simulation mode (E-04):
By setting the simulation mode to simulation operation (E-04 = on), you can put VF66B (DC motor drive) to
simulation mode. In simulation mode, VF66B (DC motor drive) simulates operation mode without outputting
voltages. Since VF66B (DC motor drive) does not output anything during operation in simulation mode, you
can check the sequence connected to VF66B (DC motor drive) without operating the motor connected to
VF66B (DC motor drive).
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-05 [No
function]
*1
- -
-
-
*1: There is no function to be set.
Restart prohibition time
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-06
Restart prohibition time
100 to 999
1
100
msec
Restart prohibition time (E-06):
Select the amount of time VF66B (DC motor drive) is prohibited from restarting. Normally, do not change its
Initialized data.
Current control gain adjustments
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-07
Current control proportion gain
10.0 to 200.0
0.1
100.0
%
E-08
Current control integral gain
10.0 to 500.0
0.1
100.0
%
Current control proportion gain (E-07), current control integral gain (E-08):
These functions adjust current control gain. Normally, do not change its Initialized data.