71
No.
Item
Description of function
27
Speed/voltage command
terminal block selection
When this signal is turned on, the terminal block ([VFC66-Z TB1] (AIN1)) is selected as the
speed commanding place forcibly regardless of the setting of the speed command input
(b-10). Even when the preset speed selection is input concurrently, this signal takes priority.
* When an optional board is installed, the place is changed from the [VFC66-Z TB1] (AIN1)
terminal to the terminal block of the optional board ([optional board] (AIN2) terminal) forcibly
regardless of the setting of the digital communication option selection (J-00).
Note that the protection function of the communication option is not activated when the
digital communication option selection (J-00) is set to 0 (OFF).
28
Operation command
[forward rotation]
*1
(STARTF)
When "1" (Terminal block) is set to the Operation command input selection (b-11) and this
signal is set to "ON," the motor starts running.
29
Operation command
[reverse rotation]
(STARTR)
When "1" (Terminal block) is set to the Operation command input selection (b-11) and this
signal is set to "ON," the motor starts running in reverse.
30
JOG command [forward
rotation]
(JOGF)
When "1" (Terminal block) is set to the JOG command input selection (b-12) and this signal is
set to "ON," the motor jogs forward.
31
JOG command [reverse
rotation]
(JOGR)
When "1" (Terminal block) is set to the JOG command input selection (b-12) and this signal is
set to "ON," the motor jogs in reverse.
32
Emergency stop
(Normally open)
This is an emergency stop signal through Normally open contact input. When the contact is
short circuited, VF66B (DC motor drive) urgently stops.
When the contact is closed,
is displayed on the console panel.
33
Protection reset
(RESET)
Setting this signal to "ON" during the protection operation will release the protection operation.
34 to 37 External signal input
When an external signal is input, the fact that a signal is input from external is sent to the
master via an optional board (communication).
*1: Do not set the operation command [forward rotation] (STARTF) because this function is usually assigned to the control
input terminal block [VFC66-Z TB1] (ST-F).
7.5. Area d (Acceleration/Deceleration Time Setting, Speed Jump Function, MRH Function
Setting Area)
Selections and settings of acceleration/deceleration time
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
d-00
Acceleration/deceleration time
selection
0: Acceleration/deceleration time (1)
1: Acceleration/deceleration time (2)
2: Acceleration/deceleration time (3)
3: Acceleration/deceleration time (4)
- 0
-
d-01
JOG acceleration/deceleration time
selection
0: Acceleration/deceleration time (1)
1: Acceleration/deceleration time (2)
2: Acceleration/deceleration time (3)
3: Acceleration/deceleration time (4)
- 1
-
d-02
Acceleration time (3)
0.0 to 3600.0
0.1
30.0
sec
d-03
Deceleration time (3)
0.0 to 3600.0
0.1
30.0
sec
d-04
Acceleration time (4)
0.0 to 3600.0
0.1
30.0
sec
d-05
Deceleration time (4)
0.0 to 3600.0
0.1
30.0
sec
d-06
S-pattern acceleration/deceleration
usage selection
oFF (Unused)
on (Used)
- oFF
-
d-07
S-pattern rise time (1)
0.0 to 60.0
0.1
0.1
sec
d-08
S-pattern acceleration reach time (1)
0.0 to 60.0
0.1
0.1
sec
d-09
S-pattern fall time (1)
0.0 to 60.0
0.1
0.1
sec
d-10
S-pattern deceleration reach time (1)
0.0 to 60.0
0.1
0.1
sec