35
Console
panel
monitor
display
Contents
Setting range (selecting item)
Factory-
initialized
data
Unit
Driving
ReWrite
d-32
Maximum deviation (negative)
-100.0 to 0.0
* The maximum speed (A-00) is 100%
-5.0 %
6.6. Area E (Current Cotrol Gain, Output Voltage Limit Related Setting Area)
Symbols of Driving ReWrite
: ReWrite is possible, ×: ReWrite is not possible
Console
panel
monitor
display
Contents
Setting range (selecting item)
Factory-
initialized
data
Unit
Driving
ReWrite
E-00
Regeneration stall prevention function
usage selection
oFF (Unused)
on (Used)
oFF -
×
E-01
Regeneration stall prevention voltage
(200 V class) 320 to 360
340
V
(400V class) 640 to 720
680
E-02 [No
function]
-
-
-
-
E-03
Forward direction change
oFF (Forward rotation)
on (Reverse rotation)
oFF -
×
E-04 Simulation
mode
oFF (Without simulation operation)
on (With simulation operation)
oFF -
×
E-05 [No
function]
-
-
-
-
E-06
Restart prohibition time
100 to 999
100 msec
E-07
Current control proportion gain
10.0 to 200.0
100.0
%
E-08
Current control integral gain
10.0 to 500.0
100.0
%
E-09 [No
function]
-
-
-
-
E-10
[For special adjustment]
oFF (Not compensated)
on (Compensated)
oFF -
×
E-11
Forward direction output maximum
voltage
80.0 to 120.0
* Rated motor armature voltage (A-03) is 100%
105.0 %
×
E-12
Reverse direction output maximum
voltage
-120 to -80.0
* Rated motor armature voltage (A-03) is 100%
-105.0 %
×
E-13
Limit width of the voltage
corresponding to the speed
5 to 120
30
V
×
E-14
[For special adjustment]
10.0 to 200.0
100.0
%
×
E-15
Armature current detection DCCT
selection
0: Auto
1: P-side DCCT
2: N-side DCCT
0 -
×
E-16
Output voltage upon rated speed
(200 V class) 70 to 230
220
V
(400V class) 140 to 460
440
E-17 [No
function]
-
-
-
-
E-18 [No
function]
-
-
-
-