9
Chapter 2 How to Connect VF66B (DC motor drive)
2.1. How to Connect VF66B (DC motor drive)
2.1.1. How to Connect VF66B (DC motor drive) Terminals
TB2
SW2
SW4
ON
CN1
CN2
Optional board
(Example: Speed sensor (PG) input
board [PG66-Z])
A
B
G
G
U/Z
V
W
G
PGOUT
ON
(Note 3)
DCL
49B
DBR
Noise filter
option
Noise filter
option
52M
MCCB
52M
(Note 4)
200 to 220V
400 to 460V
50/60Hz
86F 49F
MCCB-F
FM
49B
DBR
Dynamic braking
resistor option
Dynamic braking
unit option
External console panel
(optional)
(Note 3)
(Note 3)
(Note 4)
(Note 5)
(Note 6)
B
-
R/L1
S/L2
T/L3
MR
MT
P
N
+ 1
+ 2
TB1
CN-SO
CN-SI
RY1
CN3
SW2
SW1
CN4
LED1
52MA
86Aa
86Ab
P
COM
GND
+10
PS
PS
MI3
GND
GND
52MA
86A
MO1
MO2
AOT1
AIN1
ST-F
MI1
MI2
MI4
MI5
CN5
3
1
ON
RY2
CN6
SET66-Z
CN7
CN4
VFC66-Z
SET66EX-Z
Operation
Protection
Multifunction output terminals (MO1, MO2)
Analog output terminal (AOT1)
Analog input terminal (AIN1)
Forward operation (ST-F)
Multifunction input terminals (MI1 to MI5)
Speed sensor (PG) input terminals (A to G)
DCM
A
F
LC filter
P
PR
N
400 V class:
200 V class:
VFDB2009
52MAX
CN3
CN2
1
4 8 9
TB2
CN6
CN1
CN2 CN3
DBIF2009-Z
(Note 7)
VF66B (DC motor drive)
protection contact
(Note 1) You can change the control input terminal (ST-F) and multifunction input terminals (MI1 to MI5) to GND common input (sync
input). In this case, remove a jumper socket on the printed control board [VFC66-Z] from [CN-SO] and then attach it to [CN-SI].
(In the factory default, these are set to PS common input (source input).)
(Note 2) Never connect the GND and COM terminals of the control circuit to the ground terminal.
(Note 3) When the thermal relay of the dynamic braking resistor (DBR) operates, cut off the input of VF66B (DC motor drive).
(Note 4) Install the main circuit contactor (52M) according to the use of the customer.
When installing the main circuit contactor (52M) on the input side of VF66B (DC motor drive), wait for ten minutes or more from
the time the power is turned off until it is turned on again.
(Note 5) When DCL is not connected, terminals
1 and
2 are short-circuit.
(Note 6) The AC power supply terminals (MR/MT terminals) for the control circuit are provided to the models VF66B-1122, VF66B-1144
and higher. (These do not need to be connected to the power supply in a normal situation. Connect them only when the control
circuit power supply needs to be turned on exclusively, for example, when having the protection display while the main circuit
power supply is turned off.)