90
Analog input monitor display selection
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
G-16
Analog input monitor display selection
1: Analog input (1) [VFC66-Z TB1] (AIN1)
2: Analog input (2) [optional board] (AIN2)
3: Analog input (3) [optional board] (AIN3)
4: Analog input (4) [optional board] (AIN4)
5: Analog input (5) [optional board] (AIN5)
- 1
-
Analog input monitor display selection (G-16):
In this parameter, set the channel of the analog input to be displayed in "Analog input voltage
"
in
the monitor item of the console panel (SET66-Z).
・
Analog input (1) [AIN1] (G-16 = 1):
In "Vin," displays the voltage value that is input to analog input (1) of [VFC66-Z TB1] (AIN1).
・
Analog input (2) [AIN2] (G-16 = 2):
In "Vin," displays the voltage value that is input to analog input (2) of [option board] (AIN2).
・
Analog input (3) [AIN3] (G-16 = 3):
In "Vin," displays the voltage value that is input to analog input (3) of [option board] (AIN3).
・
Analog input (4) [AIN4] (G-16 = 4):
In "Vin," displays the voltage value that is input to analog input (4) of [option board] (AIN4).
・
Analog input (5) [AIN5] (G-16 = 5):
In "Vin," displays the voltage value that is input to analog input (5) of [option board] (AIN5).
Motor protection temperature
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
G-17
Motor protection temperature
150 to 180
1
150
°C
Motor temperature protection (G-17):
This setting is enabled when the temperature detection option <TVPT66-Z> or <TVTH66-Z> is installed.
When the motor overheat protection operation selection <F-06> is set to "ON" , set a temperature for
activating the motor overheat protection.
Normally, do not change its Initialized data of 150
℃
.