E6581442
11
K-30
[29] Communication function [1/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control V/f Constant Reference
0784 Data1
0~255 1/1
0
*1
●
/
●
●
/
●
●
●
*2
0785 Data2
0~255
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0786 Data3
0~255
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0787 Data4
0~255
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0788 Data5
0~255
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0789
MAC address
Data6 0~255
1/1
0 *1
●
/
●
●
/
●
●
●
*2
0792 Data1
0000~FFFF 1/1
0
*1
●
/
●
●
/
●
●
●
*2
0793 Data2
0000~
FFFF
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0794 Data3
0000~
FFFF
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0795 Data4
0000~
FFFF
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0796 Data5
0000~ FFFF
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0797 Data6
0000~
FFFF
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0798 Data7
0000~
FFFF
1/1
0
*1
●
/
●
●
/
●
●
●
*2
0799
Device name
Data8 0000~
FFFF
1/1
0 *1
●
/
●
●
/
●
●
●
*2
0800
Communication speed (2-wire
RS485)
0:9600 bps
1:19200 bps
2:38400 bps
1/1 1
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0801
Parity (common to 2-wire
RS485 and 4-wire RS485)
0:Non parity
1:Even parity,
2:Odd parity
1/1 1
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0802
Inverter number (common)
0~247
1/1
0
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0803
Communications time-out time
(common to 2-wire RS485 and
4-wire RS485)
0:OFF, 1~100 sec.
1/1
0
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0804
Communications time-out action
(common to 2-wire RS485 and
4-wire RS485)
0~8 1/1
8
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0805
Send waiting time (2-wire
RS485)
0.00:Default, 0.01~2.00 sec.
0.01/0.01
0.00
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0806
Master/slave setting for
inverter-to-inverter
communications (2-wire RS485)
0:Slave (issues a 0Hz command if something
goes wrong with the master)
1:Slave (continues operation if something goes
wrong with the master)
2:Slave (trips for emergency stop if something
goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque command)
1/1 0
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0807
Protocol selection (2-wire
RS485)
0:TOSHIBA
1:MODBUS
1/1 0
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
*1: This parameter is Read only.
*2: