K-7
E6581442
11
[4] Terminal response time setup
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0140
Input terminal 1 response time
selection (F)
2~200ms 1/1
8
Disabled
●
/
●
●
/
●
●
●
7.
2.
3
0141
Input terminal 2 response time
selection (R)
2~200ms 1/1
8
Disabled
●
/
●
●
/
●
●
●
7.
2.
3
0142 *6
-
-
-
-
-
-
-
-
-
0143
Input terminal 4 response time
selection (RES)
2~200ms 1/1
8
Disabled
●
/
●
●
/
●
●
●
7.
2.
3
0144
Input terminal 5~12 response
time selection
2~200ms 1/1
8
Disabled
●
/
●
●
/
●
●
●
7.
2.
3
0145
Input terminal 13~20 response
time selection
5~200ms 1/1
8
Disabled
●
/
●
●
/
●
●
●
7.
2.
3
0164 Input terminal selection 17(B12) 0~135 *1
1/1
0
Disabled
●
/
●
●
/
●
●
●
7.
2.
1
0165 Input terminal selection 18(B13) 0~135 *1
1/1
0
Disabled
●
/
●
●
/
●
●
●
7.
2.
1
0166 Input terminal selection 19(B14) 0~135 *1
1/1
0
Disabled
●
/
●
●
/
●
●
●
7.
2.
1
0167 Input terminal selection 20(B15) 0~135 *1
1/1
0
Disabled
●
/
●
●
/
●
●
●
7.
2.
1
0168
Output terminal function
selection 10 (R3) *5
0~255 *2
1/1
254
Disabled
●
/
●
●
/
●
●
●
7.
2.
2
0169
Output terminal function
selection 11 (R4) *5
0~255 *2
1/1
254
Disabled
●
/
●
●
/
●
●
●
7.
2.
2
0170
Base frequency 2
25.0~500.0 Hz
0.1/0.01
*4
Disabled
-
-
-
●
6.
4.
1
0171
Base frequency voltage 2
50~330V/660V
1/0.1
*3
Disabled
-
-
-
●
6.
4.
1
0172
Manual torque boost 2
0.0~30.0%
0.1/0.1
*3
Enabled
-
-
-
●
6.
4.
1
0173
Thermal protection level 2
10~100%
1/1
100
Enabled
-
-
-
●
6.
4.
1
0174
Base frequency 3
25.0~500.0 Hz
0.1/0.01
*4
Disabled
-
-
-
●
6.
4.
1
0175
Base frequency voltage 3
50~330V/660V
1/0.1
*3
Disabled
-
-
-
●
6.
4.
1
0176
Manual torque boost 3
0.0~30.0%
0.1/0.1
*3
Enabled
-
-
-
●
6.
4.
1
0177
Thermal protection level 3
10~100%
1/1
100
Enabled
-
-
-
●
6.
4.
1
0178
Base frequency 4
25.0~500.0 Hz
0.1/0.01
*4
Disabled
-
-
-
●
6.
4.
1
0179
Base frequency voltage 4
50~330V/660V
1/0.1
*3
Disabled
-
-
-
●
6.
4.
1
0180
Manual torque boost 4
0.0~30.0%
0.1/0.1
*3
Enabled
-
-
-
●
6.
4.
1
0181 Thermal
protection
level
4
10~100% 1/1
100
Enabled
-
-
-
●
6.
4.
1
*1:
For the adjustment range, see the table on page K-43.
*2:
For the adjustment range, see the table on page K-45.
*3: Default values vary depending on the capacity.
See the table of K-48.
*4: Inverter with a model number ending with -WN1: 60.0 -WP1: 50.0
*5: Unsupported option
*6: