E6581442
B-12
2
Terminal
symbol
Input/
output
Function (Sink Source logic)
Electrical
specifications
Inverter internal circuits
PWR
*2
Input
If P24/PLC and PWR are short-circuited, the
motor is put into a standby state. And if the
circuit between them is opened, the motor
coasts and stops. These terminals can be used
for interlock.
This terminal is not a multifunction
programmable input terminal. It is a terminal
with the power removal function that complies
with SIL II of the safety standard IEC61508 and
the requirements for category 3 of EN954-1.
Regardless of the
setting of SW1
ON: DC17V or more
OFF: Less than DC2V
(OFF: Coast stop)
Output
24Vdc power output (when SW1 is in any
position other than PLC)
24V internal output terminal
24Vdc-200mA -
P24/
PLC
Input
If SW1 is turned to the PLC position, this
terminal can be used as a common terminal
when an external power supply is used.
- -
CC *1
Common
to input/
output
Digital signal equipotential (0V) terminal for the
control circuit and equipotential (0V) terminal
for an optional control power supply backup.
- -
PP
Output
Analog input setting power output
10Vdc
(Permissible load
current:10mAdc)
RR/S4 Input
SW3: Multifunction programmable analog input
terminal when SW3 is in the RR position.
Standard default setting:0~10Vdc input and
0~60Hz frequency.
10Vdc
(Internal impedance:30 k
Ω
)
VI/I I
Input
Multifunction programmable analog input.
Standard default setting: 0~10Vdc input and
0~60Hz frequency.
This terminal can also be used as a 4-20mAdc
(0-20mAdc) input terminal, if the parameter
set to
.
10Vdc
(Internal impedance:30 k
Ω
)
4~20mA
(Internal impedance:242
Ω
)
RX Input
Multifunction programmable analog input.
Standard default setting:0~±10Vdc input and
0~±60Hz frequency.
10Vdc
(Internal impedance:22 k
Ω
)
FM Output
Multifunction programmable analog output.
Standard default setting: output frequency
Use this terminal to connect a 1mAdc full-scale
ammeter. This terminal can also be used as a
0-10V (
=
) or 0-20mA terminal
(
=
), if the SW2 switch is set to
0-10V/0-20mA side.
1mA full-scale DC
ammeter (Allowable load
resistance 7.5k
Ω
or less)
or 7.5Vdc-1mA full-scale
DC voltmeter
0-10V full-scale DC
voltmeter (Allowable
load resistance 500
Ω
or
more)/0-20mA (4-20mA)
Full-scale DC ammeter
voltmeter (Allowable
load resistance 500
Ω
or
less)
AM Output
Multifunction programmable analog output.
Standard default setting: output current
Use this terminal to connect a 1mAdc full-scale
ammeter or 7.5Vdc (10Vdc)-1mA full-scale
voltmeter.
1mA full-scale DC
ammeter ammeter
(Allowable load
resistance 7.5k
Ω
or less)
or 7.5Vdc-1mA full-scale
DC voltmeter
OUT1
Multifunction programmable open collector
output. The default setting is to output a signal
when output low speed threshold has been
reached. Depending on the SW4 setting, pulses
are output with frequencies of 1.00kHz to
43.20kHz. Standard default setting:3.84kHz
OUT2
Multifunction programmable open collector
output. By default, it is set to output a signal
indicating the completion of acceleration or
deceleration.
NO
Output
Digital output signal equipotential (0V) terminal
for the control circuit. It is isolated from the CC
terminal.
Open collector output
24Vdc-50mA
*Sink logic/source
logic switchable
P15
15k
7k
S4
P5
RR
SW3
12.7k
2.2k
15k
20
P24
OUT1
OUT2
SW4
PULS
LO
20
NO
15V
Constant
voltage
circuit
4.7k
+
-
P5
27k
10k
PWR
P24/PLC
SOURCE
P24
SINK
CPU
SW1
P5
15k
15k
242
SW2
+
-
+
-
4.7k
120
70
0-1mA
0-20mA
0-10V
0-20mA
0-10V