E6581442
11
K-32
[29] Communication function [3/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control V/f Constant Reference
0825
Send waiting time (4-wire
RS485)
0.00:Default, 0.01~2.00 sec.
0.01/0.01
0.00
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0826
Inverter-to-inverter
communication setting (4-wire
RS485)
0:Slave (issues a 0Hz command if something
goes wrong with the master)
1:Slave (continues operation if something goes
wrong with the master)
2:Slave (trips for emergency stop if something
goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5:Master (sends a torque command)
6:Master (sends an output torque command)
1/1 0
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0829
Protocol selection (4-wire
RS485)
0:TOSHIBA
1:MODBUS
1/1 0
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0830
Communication option setting 1 0~7 1/1
0
Enabled
●
/
●
●
/
●
●
●
*1
0831
Communication option setting 2 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0832
Communication option setting 3 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0833
Communication option setting 4 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0834
Communication option setting 5 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0835
Communication option setting 6 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0836
Communication option setting 7 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0837
Communication option setting 8
0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0838
Communication option setting 9
0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0841
Communication option setting 10 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0842
Communication option setting 11 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0843
Communication option setting 12 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0844
Communication option setting 13 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0845
Communication option setting 14 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0846
Communication option setting 15 0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0847
Communication option setting 16
0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0848
Communication option setting 17
0000~
1/1
0000
Enabled
●
/
●
●
/
●
●
●
*1
0849
Communication2 time-out
condition selection
0:Disconnection detection
1:When communication mode enable
2:1+Driving operation
1/1 0
Enabled
●
/
●
●
/
●
●
●
*1
0850
Disconnection detection
extended time
0.0~100.0 sec.
0.1/0.1
0.0
Enabled
●
/
●
●
/
●
●
●
*1
0851
Inverter operation at
disconnection
0:Inverter stop, communication command,
frequency mode open (by
,
)
1:None (continued operation)
2:Deceleration stop
3:Coast stop
4:Network error (
trip)
5:Preset speed operation (by
setting)
1/1 0
Enabled
●
/
●
●
/
●
●
●
*1
0852
Preset speed operation
selection
0:None
1~15:Preset speed operation (by parameter
setting)
1/1 0
Enabled
●
/
●
●
/
●
●
●
*1
*1:
For details, refer to Instruction Manual (E6581281, E6581343) specified in Section 6.42.