E6581442
11
K-26
[27] Meter output [2/2]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control V/f Constant Reference
0684
FM output filter
0:No filter
1:Filter approx. 10ms
2:Filter approx. 15ms
3:Filter approx. 30ms
4:Filter approx. 60ms
5:Filter approx. 120ms
6:Filter approx. 250ms
7:Filter approx. 500ms
8:Filter approx. 1s
1/1 0
Enabled
●
/
●
●
/
●
●
●
5.
16
0685
AM output gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1
Enabled
●
/
●
●
/
●
●
●
6. 35. 3
0686
AM bias adjustment
-10.0~100.0%
0.1/0.1
0.0
Enabled
●
/
●
●
/
●
●
●
6. 35. 3
0688
MON1 voltage/current output
switching
0:Voltage -10~10V output
1:Voltage 0~10V output
2:Current 0~20mA output
1/1 1
Disabled
●
/
●
●
/
●
●
●
*1
0689
MON1 output gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1
Enabled
●
/
●
●
/
●
●
●
*1
0690
MON1 bias adjustment
-10.0~100.0%
0.1/0.1
0.0
Enabled
●
/
●
●
/
●
●
●
*1
0691
MON2 voltage/current output
switching
0:Voltage -10~10V output
1:Voltage 0~10V output
2:Current 0~20mA output
1/1 1
Disabled
●
/
●
●
/
●
●
●
*1
0692
MON2 output gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1
Enabled
●
/
●
●
/
●
●
●
*1
0693
MON2 bias adjustment
-10.0~100.0%
0.1/0.1
0.0
Enabled
●
/
●
●
/
●
●
●
*1
*1:
For details, refer to Instruction Manual (E6581341) specified in Section 6.42