![Toshiba TOSVERT VF-AS1 Series Instruction Manual Download Page 263](http://html.mh-extra.com/html/toshiba/tosvert-vf-as1-series/tosvert-vf-as1-series_instruction-manual_424758263.webp)
E6581442
11
K-2
2. Basic parameter [2/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0015
V/f control mode selection
0:Constant torque characteristics
1:Voltage decrease curve
2:Automatic torque boost
3:Sensorless vector control 1 (speed)
4:Sensorless vector control 2 (speed/torque)
5:V/f 5-point setting
6:PM control
7:PG feedback control
8:PG feedback vector control
1/1 0
Disabled
-/-
-/-
●
/-
●
/-
●
/-
-/-
-/-
-/
●
-/
●
-/-
-/-
-/-
-/-
●
/-
-/-
-/-
-/-
-/
●
-
-
-
-
-
-
●
-
-
●
●
-
-
-
●
-
-
-
5. 6
0016
Manual torque boost 1
0.0~30.0%
0.1/0.1
*1
Enabled
-
-
●
●
5.
7
0014
Base frequency 1
25.0~500.0Hz
0.1/0.01
*3
Disabled
●
/
●
●
/
●
●
●
5.
8
0409
Base frequency voltage 1
200V class:50~330V
400V class:50~660V
1/0.1 *1
Disabled
●
/
●
●
/
●
●
●
5.
8
0011 Maximum
frequency
30.0~500.0Hz
0.1/0.01 80.0 Disabled
●
/
●
●
/
●
●
●
5.
9
0012 Upper
limit
frequency
0.0~
Hz
0.1/0.01
*3
Enabled
●
/
●
-
●
●
5.
10
0013 Lower
limit
frequency
0.0~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
10
0009
Acceleration time 1
0.1~6000 sec.
0.1/0.1 *2
*1
Enabled
●
/
●
-
●
●
5.
2
0010
Deceleration time 1
0.1~6000 sec.
0.1/0.1 *2
*1
Enabled
●
/
●
-
●
●
5.
2
0213
RR/S4 input point 2
frequency
0.0~
Hz
0.1/0.01
*3
Enabled
●
/
●
-
●
●
5.
11
0204
VI/II input point 2 frequency 0.0~
Hz
0.1/0.01
*3
Enabled
●
/
●
-
●
●
5.
11
0018
Preset speed operation
frequency 1
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0019
Preset speed operation
frequency 2
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0020
Preset speed operation
frequency 3
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0021
Preset speed operation
frequency 4
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0022
Preset speed operation
frequency 5
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0023
Preset speed operation
frequency 6
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0024
Preset speed operation
frequency 7
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
5.
12
0008
Forward run/reverse run
selection (operation panel
operation)
0:Forward run
1:Reverse run
2:Forward run (Forward/reverse switchable on operation
panel)
3:Reverse run (Forward/reverse switchable on
operation panel)
1/1 0
Enabled
●
/
●
●
/
●
●
●
5.
13
*1: Default values vary depending on the capacity.
See the table of K-48.
*2: Changing the parameter
enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
*3: Inverter with a model number ending with -WN1: 60.0 -WP1: 50.0