[8] DC braking
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0250
DC braking start frequency
0.0~120.0Hz 0.1/0.01
0.0
Enabled
●
/
●
-
●
●
6.
8.
1
0251 DC
braking
current
0~100%
1/1
50 Enabled
●
/
●
-
●
●
6.
8.
1
0252
DC braking time
0.0~20.0 sec.
0.1/0.1
1.0
Enabled
●
/
●
-
●
●
6.
8.
1
0253
Forward/reverse DC braking
priority control
0:Disabled, 1:Enabled
1/1
0
Enabled
●
/
●
-
●
●
6.
8.
1
0254
Motor shaft fixing control
0:Disabled, 1:Enabled
1/1
0
Enabled
●
/
●
-
●
●
6.
8.
2
0255 0Hz
command output selection
0:Default (DC braking)
1:0Hz command
1/1 0
Enabled
-/
●
-
- -
6. 8. 3
0256
Time limit for lower-limit
frequency operation
0.0:Disabled
0.1~600.0 sec.
0.1/0.1 0.0
Enabled
●
/
●
●
/
●
●
●
6.
9
[9] Jogging operation
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0260 Jog
run
frequency
~20.0Hz 0.1/0.01
5.0
Enabled
●
/
●
-
●
●
6.
10
0261
Jog run stop pattern
0:Deceleration stop
1:Coast stop
2:DC braking stop
1/1 0
Disabled
●
/
●
-
●
●
6.
10
0262
Operation panel jog run mode
0:Disabled
1:Operation panel jog run mode enabled
1/1 0
Enabled
●
/
●
-
●
●
6.
10
0264
Input from external contacts -
UP response time
0.0~10.0 sec.
0.1/0.1
0.1
Enabled
●
/
●
-
●
●
6.
11
0265
Input from external contacts -
UP frequency step
0.0~
Hz
0.1/0.01
0.1
Enabled
●
/
●
-
●
●
6.
11
0266
Input from external contacts -
DOWN response time
0.0~10.0 sec.
0.1/0.1
0.1
Enabled
●
/
●
-
●
●
6.
11
0267
Input from external contacts -
DOWN frequency step
0.0~
Hz
0.1/0.01
0.1
Enabled
●
/
●
-
●
●
6.
11
0268 Initial
UP/DOWN
frequency
~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
6.
11
0269
Initial up/down frequency
rewriting
0:Not changed
1:Setting of
changed when power is
turned off
1/1 1
Enabled
●
/
●
-
●
●
6.
11
[10] Jump frequency
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0270
Jump frequency 1
0.0~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
6.
12
0271 Jumping
width
1
0.0~30.0Hz
0.1/0.01 0.0 Enabled
●
/
●
-
●
●
6.
12
0272
Jump frequency 2
0.0~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
6.
12
0273 Jumping
width
2
0.0~30.0Hz
0.1/0.01 0.0 Enabled
●
/
●
-
●
●
6.
12
0274
Jump frequency 3
0.0~
Hz
0.1/0.01
0.0
Enabled
●
/
●
-
●
●
6.
12
0275 Jumping
width
3
0.0~30.0Hz
0.1/0.01 0.0 Enabled
●
/
●
-
●
●
6.
12