E6581442
J-7
10
Selection table of separate-type options (2/2)
Voltage
class
Appli-cable
motor
[kW]
Inverter
model
Input AC reactor
(ACL)
DC reactor
(DCL)
(*5)
Braking resistor
(*1)
Motor end
surge voltage
suppression
filter (*4)
Control
power
supply
backup
0.4 VFAS1-2004PL
DCL2-2004
0.75 VFAS1-2007PL
PFL-2005S
DCL2-2007
PBR-2007
1.5 VFAS1-2015PL
DCL2-2015
2.2 VFAS1-2022PL
PFL-2011S
DCL2-2022
PBR-2002
3.7/4.0 VFAS1-2037PL
PFL-2018S
DCL2-2037
PBR-2037
5.5 VFAS1-2055PL PFL-2025S
DCL2-2055
PBR3-2055
7.5 VFAS1-2075PL
DCL2-2075
PBR3-2075
11 VFAS1-2110PM
PFL-2050S
PBR3-2110
15 VFAS1-2150PM
18.5 VFAS1-2185PM
PBR3-2150
22 VFAS1-2220PM
PFL-2100S
30 VFAS1-2300PM
PBR3-2220
37 VFAS1-2370PM
PFL-2150S
45 VFAS1-2450PM
PFL-2200S
Built-in
55 VFAS1-2550P PFL-2300S
PBR-222W002
200V
class
75 VFAS1-2750P PFL-2400S
Attached as standard
DGP600W-B1
[DGP600W-C1]
–
0.75 VFAS1-4007PL
DCL2-4007
1.5 VFAS1-4015PL
DCL2-4015
MSF-4015Z
2.2 VFAS1-4022PL
DCL2-4022
PBR-2007
3.7/4.0 VFAS1-4037PL
PFL-4012S
DCL2-4037
PBR-4037
MSF-4037Z
5.5 VFAS1-4055PL
DCL2-4055
PBR3-4055
7.5 VFAS1-4075PL
DCL2-4075
PBR3-4075
MSF-4075Z
11 VFAS1-4110PL
PFL-4025S
DCL2-4110
PBR3-4110
15 VFAS1-4150PL
DCL2-4150
MSF-4150Z
18.5 VFAS1-4185PL
PBR3-4150
22 VFAS1-4220PL
PFL-4050S
MSF-4220Z
30 VFAS1-4300PL
PBR3-4220
37 VFAS1-4370PL
MSF-4370Z
45 VFAS1-4450PL
PFL-4100S
55 VFAS1-4550PL
MSF-4550Z
75 VFAS1-4750PL
PFL-4150S
Built-in
PBR-417W008
MSF-4750Z
90 VFAS1-4900PC
MSL-4215T
110
VFAS1-4110KPC
PFL-4300S
MSL-4314T
132
VFAS1-4132KPC
160
VFAS1-4160KPC
PFL-4400S
DGP600W-B2
[DGP600W-C2]
200
VFAS1-4200KPC
220
VFAS1-4220KPC
PFL-4600S
PB7-4200K(*2)
DGP600W-B3
[DGP600W-C3]
MSL-4481T
280
VFAS1-4280KPC
PFL-4800S
PB7-4200K(*2)
DGP600W-B4
[DGP600W-C4]
355
VFAS1-4355KPC
MSL-4759T
400
VFAS1-4400KPC
PFL-4450S
×2(parallel)
PB7-4400K(*2)
DGP600W-B3
×2(parallel)
[DGP600W-C3
×2(parallel)]
400V
class
500
VFAS1-4500KPC
PFL-4613S
×2(parallel)
Attached as standard
PB7-4400K(*2)
DGP600W-B4
×2(parallel)
[DGP600W-C4
×2(parallel)]
MSL-41188T
CPS002Z
(*1): Model in square brackets is fitted with top cover.
(*2): To use a 400V/200kW inverter or larger in combination with an external braking resistor (DGP600 series), a braking unit (PB7) with a built-in braking
resistor drive circuit is also needed.
(*3): The options are selected based on the premise that 600V HIV insulated wires (continuous allowable temperature: 75°C) are used.
(*4): Each MSF-****Z model is composed of a reactor, a resistor and a capacitor, and as a guide, use a cable 300m or less in length to connect the
inverter to the motor.
Each MSL-****T model is an output-dedicated surge suppression reactor, and as a guide, use a cable 100m or less in length (or 50m or less for a
shielded cable) to connect the inverter to the motor, although allowable cable lengths vary according to the input voltage.)
(*5): Be sure to connect DC reactor to 200V-55kW and above models and 400V-90kW and above models. (Not necessary for DC power input.)
When a 200V-55kW and above models or 400V-90 to 280kW models is replaced with new one, the reactor (model: DCL-****) used with the current
inverter can be used as-is with the new inverter. In such cases, therefore, you do not need to purchase any reactors in this table.