E6581442
11
K-4
2
. Basic parameter [4/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0007 Factory
default
setting
0: -
1:50 Hz default setting
2:60 Hz default setting
3:Factory default setting
4:Trip clear
5:Cumulative operation time cleared
6:Initialization of type information
7:Save user-defined parameters
8:Reset of user-defined parameters
9:Cumulative fan operation time record clear
10:Acceleration/deceleration time setting 0.01
sec.~600.0 sec. *1
11:Acceleration/deceleration time setting 0.1
sec.~6000sec.
1/1 0
Disabled
●
/
●
●
/
●
●
●
5.
20
0050
Registered parameter
display selection
0:Standard setting mode at turn on the power
1:Quick mode at turn on the power
2:Quick mode only
1/1 0
Enabled
●
/
●
●
/
●
●
●
5.
22
~
-
Extended parameters
Set detailed parameters shown in the following pages.
-
-
-
●
/
●
●
/
●
●
●
-
- Automatic
edit
function
-
-
-
●
/
●
●
/
●
●
●
4.
2
*1: If
is set to
, the optional communication devices DEV002Z, PDP002Z, IPE001Z and CCL001Z cannot be used with the inverter. (The personal computer communications software
PCM001Z cannot be used, either.) Furthermore, the copy function of the LED extended panel option (RKP002Z) does not work normally, so use only the parameter setting function and the
monitoring function.