K-31
E6581442
11
[29] Communication function [2/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control V/f Constant Reference
0808
Communication1 time-out
condition selection
0:Disconnection detection
1:When communication mode enable
2:1+Driving operation
1/1 0
Enabled
●
/
●
●
/
●
●
●
*1
0810
Frequency point selection
0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option
1/1 0
Enabled
●
/
●
-
●
●
6. 39. 1
0811 Point
1
setting
0-100%
1/1
0 Enabled *2
●
/
●
-
●
●
6. 39. 1
0812
Point 1 frequency
0.0~
Hz
0.1/0.01
0.0
Enabled *2
●
/
●
-
●
●
6. 39. 1
0813 Point
2
setting
0~100%
1/1
100 Enabled *2
●
/
●
-
●
●
6. 39. 1
0814
Point 2 frequency
0.0~
Hz
0.1/0.01
*6
Enabled *2
●
/
●
-
●
●
6. 39. 1
0815
Address monitor
(Modbus puls)
1~64 1/1
1
*5
●
/
●
●
/
●
●
●
*3
0816
Command selection
(Modbus puls)
0: Prohibit
1: Permit
1/1 0
Enabled
●
/
●
●
/
●
●
●
*3
0817
Number of command
(Modbus puls)
0~8 1/1
0
Enabled
●
/
●
●
/
●
●
●
*3
0818
Number of monitors
(Modbus puls)
0~8 1/1
0
Enabled
●
/
●
●
/
●
●
●
*3
0819
Command station
(Modbus puls)
0~64 1/1
0
Enabled
●
/
●
●
/
●
●
●
*3
0820
Communication speed (4-wire
RS485)
0:9600 bps
1:19200 bps
2:38400 bps
1/1 1
Enabled
●
/
●
●
/
●
●
●
6. 39. 1
0821
Baud rate
(Ethernet)
0:Automatic detection
1:10Mbps Full
2:10Mbps Half
3:100Mbps Full
4:100Mbps Half
1/1 0
Enabled
●
/
●
●
/
●
●
●
*4
0822
B
aud
rate monitor right port
(Ethernet)
0:Automatic detection
1:10Mbps Full
2:10Mbps Half
3:100Mbps Full
4:100Mbps Half
1/1 -
*5
●
/
●
●
/
●
●
●
*4
0823
Baud rate monitor left port
(Ethernet)
0:Automatic detection
1:10 Mbps Full
2:10Mbps Half
3:100Mbps Full
4:100Mbps Half
1/1 -
*5
●
/
●
●
/
●
●
●
*4
0824 (Reservation)
0:-
1:-
2:-
3:-
1/1 0
Enabled
●
/
●
●
/
●
●
●
*4
*1:
For details, refer to Instruction Manual (E6581315) specified in Section 6.42.
*2: Effective when a command value is sent by communication.
*3:
This function is for Modbus plus communication option (planning).
*4: This function is for Etherenet communication option (planning).
*5: This parameter is read only. *6: Inverter with a model number ending with -WN1: 60.0 -WP1: 50.0