K-3
E6581442
11
2. Basic parameter [3/4]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Vector control
Title
Communi
cation
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Speed
control
Torque
control
PM
control
V/f Reference
0600
Motor electronic thermal
protection level 1
10~100% 1/1
100
Enabled
●
/
●
●
/
●
●
●
5.
14
Setting Motor type
Overload
protection
OL stall
0
○
(protect)
× (not stall)
1
○
(protect)
○
(stall)
2
× (not protect)
× (not stall)
3
Standard
Motor
× (not protect)
○
(stall)
4
○
(protect)
× (not stall)
5
○
(protect)
○
(stall)
6
× (not protect)
× (not stall)
0017
Electronic thermal
protection characteristic
selection
7
VF Motor
× (not protect)
○
(stall)
1/1 0
Enabled
●
/
●
5. 14
●
●
5.
14
0701
Current/voltage unit
selection
0:%, 1:A (ampere)/V (volt)
1/1
0
Enabled
●
/
●
●
/
●
●
●
5.
15
0005
FM terminal meter
selection
0~
76
*1
1/1
0
Enabled
●
/
●
●
/
●
●
●
5.
16
0006
FM terminal meter
adjustment
- 1/1
*4
Enabled
●
/
●
●
/
●
●
●
5.
16
0670
AM terminal meter
selection
0~76 *1
1/1
2
Enabled
●
/
●
●
/
●
●
●
5.
16
0671
AM terminal meter
adjustment
- 1/1
*4
Enabled
●
/
●
●
/
●
●
●
5.
16
0300
PWM carrier frequency
1.0~16.0kHz (2.5~8.0kHz) *2
0.1/0.1
*3
Enabled
●
/
●
●
/
●
●
●
5.
17
0301
Auto-restart control
selection
0:Disabled
1:At auto-restart after momentary stop
2:When turning ST on or off
3:1+2
4:At start-up
1/1 0
Disabled
●
/
●
●
/
●
●
●
5.
18.1
0302
Regenerative power
ride-through control
0:Disabled
1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal)
4:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration power failure)
1/1 0
Disabled
●
/
●
-/-
●
●
5. 18. 2
0304
Dynamic braking
selection
0:Disabled
1:Enabled (braking resistance overload detect)
2:Enabled (braking resistance overload not detect)
1/1 0
Disabled
●
/
●
●
/
●
●
●
5.
19
0308
Dynamic braking resistance 0.5~1000
Ω
0.1/0.1
*3
Disabled
●
/
●
●
/
●
●
●
5.
19
0309
Allowable continuous
braking resistance
0.01~600.0kW 0.01/0.01
*3
Disabled
●
/
●
●
/
●
●
●
5.
19
*1:
For the adjustment range, see the table on page K-40.
*2: For 200V-55/75kW models and 400V-90kW to 400V-500kW models, the carrier frequency is between 2.5 and 8.0kHz inclusive.
*3: Default values vary depending on the capacity.
See the table of K-48.
*4: Default setting value is adjusted for connection of frequency meters "QS60T". (Between FM and CCA: Approx. 3.6V)
(Between AM and CCA: Approx. 3.6V)