Q9 ASD Installation and Operation Manual
89
RR Torque Reference 1
Program
Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Torque Control
mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control input
at the RR input terminal:
• Program
Utility Group
Frequency Mode 1
RR.
• Program
Utility Group
Command Mode
Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control from
the RR input terminal:
• Set
• Set
) — the input analog signal level that corresponds
• Set
• Set
) — the input analog signal level that corresponds
to the frequency setting at
.
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
Once set, as the RR input voltage changes, the output torque of the ASD will vary
in accordance with the above settings.
and is the output torque value that is
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
RR Torque Reference 2
Program
Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Torque Control
mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
and is the output torque value that is
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
for more information on this setting.
Direct Access Number — F215
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %