Q9 ASD Installation and Operation Manual
143
MON2 Terminal Meter Adjustment
No Path — Direct Access Only
This parameter is used to set the gain of the MON2 output terminal and is used in
conjunction with the settings of parameter
.
See parameter
for more information on this setting.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
FP Terminal Assignment
Program
Output Terminals
This parameter sets the functionality of the FP output terminal to any of the user-
selectable functions listed in
.
As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µ S.
This parameter is used in conjunction with parameter
.
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
FP Terminal Scaling
Program
Output Terminals
This parameter scales the FP output terminal by setting the pulses-per-second
output signal for a given assigned input value.
for more information on this parameter.
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.84
Changeable During Run — Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
FP Terminal Scaling
No Path — Direct Access Only
This parameter is used to select the degree of filtering to be applied to the DC bus
voltage and the output DC voltage.
Direct Access Number — F678
Parameter Type — Numerical
Factory Default — 64
Changeable During Run — Yes
Minimum — 4
Maximum — 100
Units — ms
FM Voltage/Current Output Switching
Program
AM/FM
This parameter is used to select the type of output signal provided at the FM
terminal
(i.e.
, Voltage or Current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA, respectively.
for more information on this setting.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
Direct Access Number — F681
Parameter Type — Selection List
Factory Default — 0 – 20 mA
Changeable During Run — No
FP