120
Q9 ASD Installation and Operation Manual
Number of PG Input Phases
No Path — Direct Access Only
This parameter determines the type of information that is supplied by the phase
encoder.
Settings:
1 — Single Phase
2 — Two Phase
Direct Access Number — F376
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
PG Disconnection Detection
No Path — Direct Access Only
This parameter Enables/Disables the system’s monitoring of the PG connection
status when using encoders with line driver outputs.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Settings:
0 — Disabled
1 — Enabled with Filter
3 — Enabled (Detect Momentary Power Fail)
Direct Access Number — F377
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
PG Pulses Per Revolution
No Path — Direct Access Only
This parameter is used to set the number of pulses per revolution of the
shaft-mounted encoder.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Direct Access Number — F378
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 12
Maximum — 9999
Units — Seconds
Autotuning Control
Program
Motor Settings
This parameter sets the Autotune command status.
Selecting Reset Motor Defaults for this parameter sets parameters
, and
to the factory default settings.
If selecting Autotune on Run Command, Autotune Initiated by Input
Terminal, or Autotune of Detail Parameters for this parameter set the Base
Frequency, Base Frequency Voltage, and the Motor Rated Revolutions to the
name-plated values of the motor to achieve the best possible Autotune precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see
4 — Motor Constant Auto Calculation
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No