Q9 ASD Installation and Operation Manual
59
Direct Access Parameter Information
The Q9 ASD has the ability to allow the user direct access to the motor control functions. There are two
ways in which the motor-control parameters may be accessed for modification: Program
Applicable
Menu Path or Program
Direct Access
Applicable Parameter Number.
Both methods access the
parameter via the Program mode. Once accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop an application-specific motor-control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note: Parameter selections are preceded by the number used to select an item if using communications to
write to a parameter location in memory
(i.e.
, F000
0-Manual, 1- No Trip on Acc/Dec, 2-No trip on
Acc Only, etc.).
Note: The setup procedures included within this section may require a Reset before performing the procedure.
Application-specific settings may then be performed. The pre-Reset conditions may be saved (see
).
Note: Communications setting changes will require that the power be removed and then re-applied for the
changes to take affect.
Direct Access Parameters/Numbers
Automatic Acceleration/Deceleration
No Path — Direct Access Only
This parameter is used to adjust the acceleration and deceleration rates in
accordance with the applied load automatically.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for Acceleration Time 1 (
) and Deceleration Time
1 (
).
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only
Note:
The motor and the load must be connected prior to selecting
Automatic Acceleration/Deceleration.
Direct Access Number — F000
Parameter Type — Selection List
Factory Default — Manual
Changeable During Run — No
Automatic Torque Boost
No Path — Direct Access Only
This parameter Enables/Disables the ability of the ASD to adjust the output
torque in accordance with the applied load automatically. When enabled
Autotuning is performed. The motor should be connected before performing an
Autotune.
Settings:
0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector C Autotuning
Direct Access Number — F001
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No