
Q9 ASD Installation and Operation Manual
75
LI8 Terminal
Program
Input Terminals
This parameter is used to set the functionality of the LI8 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This setting assigns the function of the programmable LI8 terminal to any of the
user-selectable functions listed in
Note:
The Expansion IO Card Option 2 Option Board (P/N ETB004Z) is
required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for more
information on the function of this terminal.
Direct Access Number — F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
OUT1 Terminal
Program
Output Terminals
This parameter is used to set the functionality of the OUT1 discrete output
terminals O1A and O1B.
The O1A and O1B (OUT1) output terminals change states (open or close) as a
function of a user-selected event. See
for listing the possible
assignments for the OUT1 terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F130
Parameter Type — Selection List
Factory Default — Damper Command
Changeable During Run — No
OUT2 Terminal
Program
Output Terminals
This parameter is used to set the functionality of the OUT2 discrete output
terminals O2A and O2B.
The O2A and O2B (OUT2) output terminals change states (open or close) as a
function of a user-selected event. See
for listing the possible
assignments for the OUT2 terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F131
Parameter Type — Selection List
Factory Default — RCH (Acc/Dec
Complete)
Changeable During Run — No
FL Terminal
Program
Output Terminals
This parameter is used to set the functionality of the FL output terminals to 1 of
the functions listed in
.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F132
Parameter Type — Selection List
Factory Default — Fault (All)
Changeable During Run — No
OUT1
Damper
Command
OUT2
Summary of Contents for Q9 Series
Page 2: ......
Page 4: ......
Page 8: ......
Page 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...