Q9 ASD Installation and Operation Manual
165
Block Read Data 5
No Path — Direct Access Only
This parameter plays a role in the setup of the communications network by
establishing the type of data to be read from the ASD of the communications link.
See parameter
for more information on this setting.
Direct Access Number — F879
Parameter Type — Selection List
Factory Default — None
Changeable During Run — Yes
Free Notes
No Path — Direct Access Only
This is an unused parameter that has allocated memory space.
The space may be used at the discretion of the user.This space may be used to
store information or a note to be transferred using communications.
Direct Access Number — F880
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 65535
Ext. Comm. Cfg. 1
No Path — Direct Access Only
This parameter sets the RS485 protocol. An improper setting will result in an
INVALID PROTOCOL error.
Settings:
0 — Modbus RTU
1 — Metasys N2
2 — Seimens FLM
Direct Access Number — F882
Parameter Type — Numerical
Factory Default — Modbus RTU
Changeable During Run — Yes
Minimum — 0
Maximum — 255 (Only 0 – 2 Effective)